MIL-PRF-12732F
w. Set up Condition C2 (table I) in the same manner as above with a flow rate of
8.5 gpm at a discharge pressure of 25 psig. Do not change range valve or dosage
control settings. Repeat steps j.l through j.9.
x. Set up Condition C3 (table I) in the same manner as above with a flow rate of 2 gpm
at a discharge pressure of 25 psig. Do not change range or dosage control settings.
Repeat steps j.1 through j.9.
y. Compare the solution application rates for Condition Cl through C3. They should be
alike within a range of ±10 percent. Compare pump rate figures recorded for
Conditions Cl through C3. They should be proportional within ±10 percent.
z. Disconnect the unit and drain water from all pipes, tubing, hoses and components,
with particular attention to assure complete draining of the water meter.
4.5.2.3.3 Failure criteria. A range deviation greater than ±10 percent on solution
application or proportionality shall constitute failure of this test.
4.5.2.4 Environmental. The unit shall be placed in a temperature-controlled chamber
and tested for conformance to 3.5.1. The unit shall be drained of all liquid for storage
environmental test. Unless otherwise specified (see 6.2), if the completely assembled unit is too
large to be placed in an environmental chamber intact, those components agreed upon, whose
integrity or performance might be adversely affected by temperature extremes may be subjected
to the environmental test individually. Evidence of deformation, deterioration, or other forms of
permanent damage, shall constitute failure of this test.
4.6 Inspection of packaging.
4.6.1 Quality conformance inspection of pack.
4.6.1.1 Unit of product. For the purpose of inspection, a completed pack prepared for
shipment shall be considered a unit of product.
4.6.1.2 Sampling. Sampling for examination shall be in accordance with
ANSI/ASQ Z1.4.
5. PACKAGING
5.1 Packaging. For acquisition purposes, the packaging requirements shall be as
specified in the contract or order (see 6.2). When packaging of materiel is to be performed by
DoD or in-house contractor personnel, these personnel need to contact the responsible packaging
activity to ascertain packaging requirements. Packaging requirements are maintained by the
Inventory Control Point s packaging activities within the Military Service or Defense Agency, or
within the military service s system commands. Packaging data retrieval is available from the
managing Military Department s or Defense Agency s automated packaging files, CD-ROM
products, or by contacting the responsible packaging activity.
6. NOTES